The HAK GA200/X-CD/HW is a multi-component analyzer system designed to measure IR absorbing gases, oxygen and many other components. This system can be installed in many industrial applications, e.g. for emission, Process and ambient monitoring.
- Multi component gas analyzers integrated in cabinet - System designed according to any customer specific application. - Automatic self-diagnoses via operator display panel. - Safe and durable shelter (optional) - Flexibility in sample probe according to the application condition (ie pressure, temp, dust, humidity, aggressive gases) - Digital and analog outputs. (inputs and out puts) eg display of parameters from the system) - User friendly maintenance
Gas analyzer
Please refer to specific manufacturer analyzer data sheet
Gas Conditioning
Sample flow
7 to 70 liter / hour
Sample temperature
Max. 200 °C (at cabinet inlet)
Dew point H20
Approx. 65 °C
General data
Installation location requirement
Air conditioning room temperature
Power supply
- 230 V (+10/–15 %), 50/60 Hz, 50 A, max 10 kVA , external max. 3.5 VA
- 400 V (+10/–15 %), 50/60 Hz, max. 12 kVA, external max. 7 kVA
- 115 V (+10/–15 %), 50/60 Hz, max. 2,5 kVA, external max. 1.7 kVA
Ambient temperature during operation
- +5 ... +35 °C without direct sunshine
- +5 ... +50 °C * with built-in air conditioning unit
IP 34
Transport and storage temperature
-20 ... +55 °C
Relative humidity
Class F (DIN 40 040)
75 % annual average
95 % temporary, not-condensing
Dimensions
Sheet steel cabinet 2100 x 800 x 600 mm
Also according to customer application
Color
RAL 7032
Protection type
IP 20 or IP 54 on request